In raised floor data centers, tiles with high open area ratio or complex understructure are used to fulfill the demand of today's high-density computing. Using more open tiles reduces the pressure drop across the raised floor with the potential advantages of increased airflow and lower noise. However, it introduces the disadvantage of increased nonuniformity of airflow distribution. In addition, there are various tile designs available on the market with different opening shapes or understructures. Furthermore, a physical separation of cold and hot aisles (containment) has been introduced to minimize the mixing of cold and hot air. In this study, three types of floor tiles with different open area, opening geometry, and understructure are considered. Experimentally validated detail models of tiles were implemented in computational fluid dynamics (CFD) simulations to address the impact of tile design on the cooling of information technology (IT) equipment in both open and enclosed aisle configurations. Also, impacts of under-cabinet leakage on the IT equipment inlet temperature in the provisioned and under-provisioned scenarios are studied. In addition, a predictive equation for the critical under-provisioning point that can lead to a no-flow condition in IT equipment with weaker airflow systems is presented. Finally, the impact of tile design on thermal performance in a partially enclosed aisle with entrance doors is studied and discussed.
Skip Nav Destination
Article navigation
March 2018
Research-Article
Impact of Tile Design on the Thermal Performance of Open and Enclosed Aisles
Sadegh Khalili,
Sadegh Khalili
Department of Mechanical Engineering,
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
Search for other works by this author on:
Mohammad I. Tradat,
Mohammad I. Tradat
Department of Mechanical Engineering,
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
Search for other works by this author on:
Kourosh Nemati,
Kourosh Nemati
Future Facilities Inc.,
San Jose, CA 95110
San Jose, CA 95110
Search for other works by this author on:
Mark Seymour,
Mark Seymour
Future Facilities Ltd.,
London SE1 7HX, UK
London SE1 7HX, UK
Search for other works by this author on:
Bahgat Sammakia
Bahgat Sammakia
Department of Mechanical Engineering,
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
Search for other works by this author on:
Sadegh Khalili
Department of Mechanical Engineering,
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
Mohammad I. Tradat
Department of Mechanical Engineering,
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
Kourosh Nemati
Future Facilities Inc.,
San Jose, CA 95110
San Jose, CA 95110
Mark Seymour
Future Facilities Ltd.,
London SE1 7HX, UK
London SE1 7HX, UK
Bahgat Sammakia
Department of Mechanical Engineering,
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
ES2 Center,
Binghamton University-SUNY,
Binghamton, NY 13902
Contributed by the Electronic and Photonic Packaging Division of ASME for publication in the JOURNAL OF ELECTRONIC PACKAGING. Manuscript received October 13, 2017; final manuscript received November 28, 2017; published online March 2, 2018. Assoc. Editor: Reza Khiabani.
J. Electron. Packag. Mar 2018, 140(1): 010907 (12 pages)
Published Online: March 2, 2018
Article history
Received:
October 13, 2017
Revised:
November 28, 2017
Citation
Khalili, S., Tradat, M. I., Nemati, K., Seymour, M., and Sammakia, B. (March 2, 2018). "Impact of Tile Design on the Thermal Performance of Open and Enclosed Aisles." ASME. J. Electron. Packag. March 2018; 140(1): 010907. https://doi.org/10.1115/1.4039028
Download citation file:
Get Email Alerts
Computational Framework for Computational Fluid Dynamics Analysis of Loop Thermosiphon Based Embedded Cooling Systems
J. Electron. Packag (September 2025)
Flow Characterization of Capillary Underfill in Multi-Chip Heterogenous Integration Using Computational Fluid Dynamics
J. Electron. Packag (September 2025)
Related Articles
Experimentally Validated Computational Fluid Dynamics Model for a Data Center With Cold Aisle Containment
J. Electron. Packag (June,2015)
Experimental and Computational Investigations of the Thermal Environment in a Small Operational Data Center for Potential Energy Efficiency Improvements
J. Electron. Packag (September,2020)
Experimental and Numerical Analysis of Data Center Pressure and Flow Fields Induced by Backward and Forward CRAH Technology
J. Electron. Packag (September,2022)
Airflow and Cooling in a Data Center
J. Heat Transfer (July,2010)
Related Proceedings Papers
Related Chapters
Compressive Deformation of Hot-Applied Rubberized Asphalt Waterproofing
Roofing Research and Standards Development: 10th Volume
On the Average Diameter of Directed Double-Loop Networks
International Conference on Instrumentation, Measurement, Circuits and Systems (ICIMCS 2011)
System Thermal Analysis-Rack (Part II)
Thermal Management of Telecommunication Equipment, Second Edition